欢迎光临流量计制造(江苏)有限公司官网!

数显式微差压变送器

  1. 自整流、自清洗、自保护特性.
数显式微差压变送器技术规格:

 量程

  

 

  LFM110 -1000~+1000Pa 小可设0~+100Pa

  LFM112 -10,000~+10,000Pa 小可设0~+1000Pa

  LFM116 -100~+100Pa 小可设0~+10Pa

  LFM111 -3400~+3400Pa 小可设0~+100Pa

  

 

  精确度

  

 

  ±1.0%FS

  

 

  压力单位

  

 

  Pa, mmH2O, mbar, inWG, mmHG, daPa, KPa, hPa

  

 

  输出信号

  

 

  0~5VDC、0~10VDC、4~20mA、RS-485信号

  (模拟信号:电流型两线制、电压型三线制、电流电压同时输出六线制;数字信号:RS-485四线制)

  

 

  电源供应

  

 

  两组同时输出,输入电压为16~30VAC/VDC,可配24VDC适配器(3.5×1.35mm)供电

  4~20mA(两线制)输出,输入电压为无极性①的12~30VDC

  0~5/10VDC输出,输入电压为16~30 VAC/VDC

  RS-485输出,输入电压为12~30VAC/VDC

  

 

  功耗

  

 

  ≤1.5W

  

 

  ① 无极性:输入电压源接线不分正负极方向



数显式微差压变送器功能:

响应时间

  

 

  0.5s,1s,2s,4s

  

 

  分辨率

  

 

  LFM110

  LFM112

  

 

  1Pa,0.1mmH2O,0.01mbar,0.004inWG,

  0.007mmHG,0.1dapa,0.001KPa,0.01hPa

  

 

  LFM116

  

 

  0.1Pa,0.01mmH2O,0.01mbar,0.01dapa,0.001hPa

  

 

  LFM111

  

 

  1Pa,0.1mmH2O,0.01mbar,0.004inWG,

  

 

  零点校准

  

 

  手动按键零点校准

  

 

  测量介质

  

 

  空气和中性气体

  

 

  允许过压

  

 

  15KPa(LFM110);150KPa(LFM112);4.5KPa(LFM116);60KPa(LFM111)

  

 

  使用温度

  

 

  -10~+60℃

  

 

  存储温度

  

 

  -10~+70℃

  



上一篇:智能微差压变送器